Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
156
05/2014
Table 62: Circuit Breaker Selection Options
Model Number NT NW NW
Frame type T W Y (wide-construction)
Maximum frame rating
ANSI UL UL IEC ANSI ANSI UL IEC ANSI UL IEC
800 A 1200 A 1600 A 1600 A 3200 A 4000 A 3000 A 4000 A 6000 A 6000 A 6300 A
Maximum Interrupting Rating (kA, 50/60 Hz)
AC rating
254 V
42 kA
240 V
200 kA
240 V
200 kA
240 V
150 kA
254 V
200 kA
254 V
100 kA
240 V
200 kA
240 V
150 kA
254 V
200 kA
240 V
200 kA
240 V
150 kA
508 V
42 kA
480 V
100 kA
480 V
100 kA
440 V
130 kA
508 V
200 kA
508 V
100 kA
480 V
150 kA
440 V
150 kA
508 V
200 kA
480 V
150 kA
440 V
150 kA
635 V
N/A
600 V
50 kA
600 V
50 kA
690 V
42 kA
635 V
130 kA
635 V
85 kA
600 V
100 kA
690 V
100 kA
635 V
130 kA
600 V
100 kA
690 V
100 kA
Construction
Drawout XX—XX—XXXXX
Fixed (UL Listed and IEC Rated only) X X X X X X X X X X X
Termination
Rotatable rear terminals XXXXXXXXXXX
Front-connected terminals X X X X X X X X X X X
Accessories Available for the Circuit Breaker and Cradle
• Shunt close • Ready-to-close contact • Door interlock
• Shunt trip • Overcurrent trip switch (standard) • Operations counter
• Undervoltage trip • Rack in interlock • Safety Shutter
• Fixed time delay • Key locks for circuit breaker and cradle • Cradle rejection kit (standard)
• Adjustable time delay • Padlock attachment (circuit breaker plus cradle) • Rail Padlocking
• Spring-charging motor • Mechanical interlocks
• Auxiliary contacts (standard) • Cradle position switches
Electronic Trip Unit Features
• True RMS sensing • Trip indication LED • Neutral protection
• LSI • Zone-selective interlocking (ZSI) • Contact wear indication
• Ground-fault alarm (no trip) • Communications • Incremental fine-tuning of settings
• Ground-fault trip • LCD dot matrix display • Selectable long-time delay bands
• Ground-fault trip and programmable alarm • Advanced user interface • Power measurement
• Adjustable rating plugs • Protective relay functions • Expanded memory
• Long-time pickup LED • Thermal imaging • Enhanced power quality measurement
Table 63: Micrologic Trip Unit Selection
Design Platform Designation Feature Type Protection Model Number
Basic Trip Unit Basic
LS0 (IEC Rated) 2.0
LI (UL Listed/ANSI Certified) 3.0
LSI 5.0
Trip Unit with Ammeter A
LS0 (IEC Rated) 2.0A
LI (UL Listed/ANSI Certified) 3.0A
LSI 5.0A
LSIG 6.0A
Trip Unit with Power Metering P
LSI 5.0P
LSIG 6.0P
Trip Unit with Harmonic Metering H
LSI 5.0H
LSIG 6.0H