Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
165
05/2014
© 2000–2014 Schneider Electric
All Rights Reserved
Y-Frame Switch Selection
A
Table 82: IEC 60947-2 Rated Y-Frame Circuit Breakers
Frame Rating
Model
Number
Interrupting Rating
Sensor Plug Rating
240 V 440 V 690 V
4000 A
NW40BH1 100 kA 100 kA 100 kA 2000 A, 2500 A, 3200 A, 4000 A
NW40BH2 150 kA 150 kA 100 kA 2000 A, 2500 A, 3200 A, 4000 A
5000 A
NW50H1 100 kA 100 kA 100 kA 2500 A, 3200 A, 4000 A, 5000 A
NW50H2 150 kA 150 kA 100 kA 2500 A, 3200 A, 4000 A, 5000 A
6300 A
NW63H1 100 kA 100 kA 100 kA 3200 A, 4000 A, 5000 A, 6300 A
NW63H2 150 kA 150 kA 100 kA 3200 A, 4000 A, 5000 A, 6300 A
Table 83: ANSI C37 Certified/UL 1066 Listed, Non-Automatic Switches
Frame Rating
Model
Number
Interrupting Rating (kA)
1
1
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Short-Time (0.5 s)
Rating
254 V 508 V 635 V
4000 A NW40HA 85 kA 85 kA 85 kA 85 kA
5000 A NW50HA 85 kA 85 kA 85 kA 85 kA
Table 84: ANSI C37 Certified/UL 1066 Listed, Drawout Automatic Switches
Frame Rating
(Y-Frame)
Model
Number
Interrupting Rating
1
1
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Short-Time (0.5 s)
Rating
254 V 508 V 635 V
3200 A NW32HC
2
2
Not available in 4P.
200 kA 200 kA 130 kA 100 kA
4000 A
NW40HF 100 kA 100 kA 85 kA 85 kA
NW40HC
2
200 kA 200 kA 130 kA 100 kA
5000 A
NW50HF 100 kA 100 kA 85 kA 85 kA
NW50HC
2
200 kA 200 kA 130 kA 100 kA
Table 85: ANSI C37 Certified/UL 1066 Listed, Fixed Automatic Switches
Frame Rating
(Y-Frame)
Model
Number
Interrupting Rating
1
1
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Short-Time (0.5 s)
Rating
254 V 508 V 635 V
4000 A NW40HF 100 kA 100 kA 85 kA 85 kA
5000 A NW50HF 100 kA 100 kA 85 kA 85 kA
Table 86: UL 489 Listed, Fixed Automatic Switches
Frame Rating
Model
Number
Withstand Rating
1
1
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
Instantaneous Override
240 V 480 V 600 V
4000 A NW40HF 100 kA 100 kA 85 kA 75 kA
5000 A NW50HF 100 kA 100 kA 85 kA 75 kA
6000 A NW60HF 100 kA 100 kA 85 kA 75 kA
Commenti su questo manuale