Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
45
05/2014
© 2000–2014 Schneider Electric
All Rights Reserved
Cradle Position Switch
Three series of optional auxiliary switches are available for the cradle:
Cradle position switches (CE) to indicate the connected position.
Cradle position switches (CD) to indicate the disconnected position. This
position is indicated when the required clearance for isolation of the power
and auxiliary circuits is reached.
Cradle position switches (CT) to indicate the test position. In this position, the
power circuits are disconnected and the auxiliary circuits are connected.
Table 41: Cradle Position Switch Characteristics
Circuit Breaker Type
NT NW
1
Possible Ring-Terminal Combinations
CE CD CT CE CD CT CE CD CT
Maximum Push-In Switches with
Standard Actuators
3213
1
3
1
3
1
1b 1a 1b
1b 1a, 1b 1b
1a, 2b 1a, 2b 1a
With Additional Actuators
9 0 0 1a, 2b 2a, 1b 1b
6 3 0 2a, 1b 1a, 2b 1b
3 6 0 1a 1a 1a
6 0 3 3a 3a 1a
Breaking
Capacity at a
Power Factor
(p.f) of 0.3
Standard (100 mA/24 V minimum load) 3b 3b 1b
Vac
240 8 A 8 A
Additional Actuators for Cradle
Position Switches on Masterpact NW
Circuit Breakers
A set of additional actuators may be
installed on the cradle to change or add
the functions of the cradle position
switches. Each standard actuator can be
replaced by any other actuator to
change the function of the cradle
position switch.
380 8 A 8 A
480 8 A 8 A
600/690 6 A 6 A
Vdc
24/48 2.5 A 2.5 A
125 0.8 A 0.8 A
250 0.3 A 0.3 A
Low-Level (2 mA/15 V minimum load)
Vac
24/48 5 A 5 A
240 5 A 5 A
380 5 A 5 A
Vdc
24/48 2.5 A 2.5 A
125 0.8 A 0.8 A
250 0.3 A 0.3 A
Figure 11: Cradle Position Switch Actuators
Cradle Position
Switch (CE, CD, CT)
Actuator for up to Three
CE Switches (standard)
Actuator for up to Three
CD Switches (standard)
Actuator for up to Three
CT Switches (standard)