Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
22
05/2014
Micrologic Trip Units–Overview
True RMS Current Sensing
The sensing system responds to the flow of current through the circuit breaker. Electronic trip circuit
breakers are limited to ac systems because the electronic trip system uses current transformers to
sense the current.The Micrologic trip unit samples the current waveform to provide true RMS
protection through the 15th harmonic.
This true RMS sensing gives accurate values for the magnitude of a non-sinusoidal waveform.
Therefore, the heating effects of harmonically distorted waveforms are accurately evaluated.
The Micrologic H trip unit provides additional sampling of the waveforms to measure and provide
waveform capture of harmonic distortion to the 31st harmonic.
Masterpact universal power circuit breakers use Micrologic electronic trip systems to sense overcurrents
and trip the circuit breaker. The Micrologic basic trip unit is standard and all Masterpact circuit breakers can
be equipped with the optional Micrologic trip systems listed below:
Micrologic Basic Trip Unit (standard).
2.0 basic protection (LS0, IEC)
3.0 basic protection (LI, UL
®
/ANSI)
5.0 selective protection (LSI)
Micrologic A: Trip Unit with Ammeter.
2.0A basic protection (LS0, IEC)
3.0A basic protection (LI, UL/ANSI)
5.0A selective protection (LSI)
6.0A selective protection with ground-fault protection for equipment (LSIG)
Micrologic P: Trip Unit with Power Metering.
5.0P selective protection (LSI)
6.0P selective protection with ground-fault protection for equipment (LSIG)
Micrologic H: Trip Unit with Harmonic Metering.
5.0H selective protection (LSI)
6.0H selective protection with ground-fault protection for equipment (LSIG)
Micrologic 3.0 and 5.0 Basic Trip Units
Micrologic 3.0A, 5.0A and 6.0A Trip Units