
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
27
05/2014
© 2000–2014 Schneider Electric
All Rights Reserved
Micrologic 5.0P & 6.0P Trip Units with Power Metering
Protection Settings
Configuring Alarms and Other Protection Functions
When the cover is closed, the keypad may no longer be used to change the protection settings, but it
still provides access to the displays for measurements, histories, indicators, etc. Depending on the
thresholds and time delays set, the Micrologic P trip unit monitors current, voltage, power, frequency,
and phase sequence. Each threshold overrun may be signalled remotely via the communication
network.
Each threshold overrun may be combined with tripping (protection) or an indication carried out by an
optional M2C/M6C programmable contact (alarm), or both (protection and alarm).
Maintenance Record
The maintenance record can be consulted using the full-function test kit or remotely via the
communication network. It can be used as an aid in troubleshooting and to assist scheduling for device
maintenance operations.
Recorded indications include:
•
Highest current measured
•
Operation counter (both cumulative total and total since last reset)
•
Number of test kit connections
•
Number of trips in operating mode
•
Contact wear (Masterpact NW only)
1—Test lamp and indication
reset
2—Indication of tripping
cause
3—High resolution screen
4—Measurement display
5—Maintenance indicators
6—Protection settings
7—Navigation buttons
8—Overload signal (LED)
9—Long-time rating plug
screw
10—Long-time current
setting and tripping delay
11—Short-time pickup and
tripping delay
12—Instantaneous pickup
13—Hole for settings
lockout pin
14—Electronic push-to-trip
15—Ground-fault pickup and
tripping delay
16—Test connector
The adjustable protection functions of the 5.0P and 6.0P trip units
are identical to those of Micrologic A trip unit (overloads, short
circuits, equipment ground-fault protection); see page 25.
These units also feature:
•
Fine adjustment: Within the range below the rotary switch
setting, fine adjustments of pickups/delays in steps of 1 A/s
(except for short-time and ground-fault) are possible on the
keypad or remotely by the communication network.
•
Inverse definite minimum time lag (IDMTL) setting:
Coordination with fuse-type or medium-voltage protection systems
is optimized by adjusting the long-time delay curve around 6 x I
r
axis. This setting ensures better coordination with certain loads.
•
Neutral protection: On three-pole circuit breakers, neutral
protection may be set using the keypad or remotely using the
communication network to one of four positions:
—OFF
— 1/2N (1/2 x I
n
)
—1N (1 x I
n
)
—2N (2 x I
n
)
NOTE: The neutral protection is disabled if the long-time curve is set
to one of the IDMTL protection settings.
Micrologic 6.0P Trip Unit
Commenti su questo manuale