Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
157
05/2014
© 2000–2014 Schneider Electric
All Rights Reserved
Factory-Assembled Circuit Breakers and Switches
T-Frame Circuit Breaker Selection
NOTE: L1F and LF circuit breakers are tested to show the arc flash hazard risk category as referenced
by NFPA 70E.
Table 64: ANSI C37 Certified/UL 1066 Listed T-Frame Circuit Breakers
Frame Rating
Model
Number
Interrupting Rating
Sensor Plug Rating
254 V 508 V 635 V
800 A NT08N1 42 kA 42 kA — 100 A, 250 A, 400 A, 600 A, 800 A
Table 65: UL 489 Listed T-Frame Circuit Breakers
Frame Rating
Model
Number
Interrupting Rating
Sensor Plug Rating
240 V 480 V 600 V
800 A
NT08N 50 kA 50 kA 35 kA 100 A, 250 A, 400 A, 600 A, 800 A
NT08H 65 kA 50 kA 50 kA 100 A, 250 A, 400 A, 600 A, 800 A
NT08L1
1
1
Not available in 4P circuit breakers.
100 kA 65 kA — 100 A, 250 A, 400 A, 600 A, 800 A
NT08L
1
200 kA 100 kA — 100 A, 250 A, 400 A, 600 A, 800 A
NT08LF
1
200 kA 100 kA — 100 A, 250 A, 400 A, 600 A, 800 A
1200 A
NT12N 50 kA 50 kA 35 kA 600 A, 800 A, 1000 A, 1200 A
NT12H 65 kA 50 kA 50 kA 600 A, 800 A, 1000 A, 1200 A
NT12L1
1
100 kA 65 kA — 600 A, 800 A, 1000 A, 1200 A
NT12L
1
200 kA 100 kA — 600 A, 800 A, 1000 A, 1200 A
NT12LF
1
200 kA 5100 kA — 600 A, 800 A, 1000 A, 1200 A
1600 A
2
2
Fixed-mount only. 1600A UL 489 drawout circuit breakers are not available.
NT16N 50 kA 50 kA 35 kA 800 A, 1000 A, 1200 A, 1600 A
NT16H 65 kA 50 kA 50 kA 800 A, 1000 A, 1200 A, 1600 A
NT16L1
1
100 kA 65 kA — 800 A, 1000 A, 1200 A, 1600 A
NT16L
1
200 kA 100 kA — 800 A, 1000 A, 1200 A, 1600 A
NT16LF
1
200 kA 5100 kA — 800 A, 1000 A, 1200 A, 1600 A
Table 66: IEC 60947-2 Rated T-Frame Circuit Breakers
Frame Rating
Model
Number
Interrupting Rating (kA)
Sensor Plug Rating (A)
240 V 440 V 690 V 1000 V
800 A
NT08H1 42 kA 42 kA 42 kA — 250 A, 400 A, 630 A, 800 A
NT08L1 150 kA 130 kA 25 kA — 250 A, 400 A, 630 A, 800 A
1000 A
NT10H1 42 kA 42 kA 42 kA — 400 A, 630 A, 800 A, 1000 A
NT10L1 150 kA 130 kA 25 kA — 400 A, 630 A, 800 A, 1000 A
1250 A NT12H1 42 kA 42 kA 42 kA — 630 A, 800 A, 1000 A, 1250 A
1600 A NT16H1 42 kA 42 kA 42 kA — 800 A, 1000 A, 1250 A, 1600 A