© 2000–2014 Schneider Electric
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
24
05/2014
Micrologic 2.0, 3.0, and 5.0 Basic Trip Units
The Micrologic 2.0, 3.0, and 5.0 trip units protect power circuits.
Protection Settings
1—Overload signal (LED)
2—Long-time rating plug
screw
3—Long-time current setting
and tripping delay
4—Instantaneous pickup
5—Short-time pickup and
tripping delay
6—Test connector
Protection thresholds and delays are set using the rotary switches.
A full-range of long-time settings are available via field-
installable adjustable rating plugs.
Overload protection
True RMS long-time protection
Thermal imaging: Active thermal imaging before and
after tripping
Short-circuit protection.
Short-time RMS
Selection of I
2
t type (ON or OFF) for short-time delay
Instantaneous protection.
Neutral protection on four-pole circuit breakers.
Micrologic 5.0 Basic Trip Unit
Table 21: Micrologic 2.0 and 3.0 Basic Trip Unit Settings
Long-Time
Protection
Current Setting (A)
Tripping Between 1.05
and 1.20 x I
r
I
r
= l
n
x...
2.0: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
3.0: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
Other ranges are available by changing rating plug
Time Delay (s)
Accuracy: 0 to –20%
t
r
at 1.5 x I
r
12.5 25 50 100 200 300 400 500 600
t
r
at 6 x I
r
0.5 1 2 4 8 12 16 20 24
t
r
at 7.2 x I
r
0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal Imaging 20 minutes before or after tripping
Short-Time
Protection
Current Setting (A)
Accuracy: ±10%
No Delay
I
sd
= I
r
x... 2.0: 1.5 2 2.5 3 4 5 6 8 10
Instantaneous
Protection
Current Setting (A)
Accuracy: ±10%
I
i
= I
n
x... 3.0:1.52345681012
Table 22: Micrologic 5.0 Basic Trip Unit Settings
Long-Time
Protection
Current Setting (A)
Tripping Between 1.05
and 1.20 x I
r
I
r
= l
n
x...
IEC: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
UL/ANSI: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
Other ranges are available by changing rating plug
Time Delay (s)
Accuracy: 0 to –20%
t
r
at 1.5 x I
r
12.5 25 50 100 200 300 400 500 600
t
r
at 6 x I
r
0.51 2 4 8 12162024
t
r
at 7.2 x I
r
0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal Imaging 20 minutes before or after tripping
Short-Time
Protection
Current Setting (A)
Accuracy: ±10%
l
sd
= I
r
x... 1.522.53456810
Time Delay (s)
at 10 x I
r
Settings
I
2
t OFF 0 0.1 0.2 0.3 0.4
I
2
t ON 0.1 0.2 0.3 0.4
t
sd
Min. trip
time (ms)
20 80 140 230 350
Max. trip
time (ms)
80 140 200 320 500
Instantaneous
Protection
Current Setting (A)
Accuracy: ±10%
I
i
= I
n
x... 23468101215off
Vedere la pagina 23