Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
5
05/2014
© 2000–2014 Schneider Electric
All Rights Reserved
UL File Numbers:
Masterpact NW: E161835 Vol. 2 Sec. 1
Masterpact NT: E161835 Vol. 2 Sec. 2
Features and Benefits
High Ampere Interrupting Rating (AIR): ANSI Certified Masterpact NW circuit breakers have an
interrupting rating of 200,000 A at 508 Vac without fuses.
High Short-Time Current Rating: Masterpact NW circuit breakers have exceptional short-time
ratings—up to 100,000 A.
100% Rated Circuit Breaker: Masterpact circuit breakers are designed for continuous operation at
100% of their current rating.
Reverse Fed Circuit Breaker: Masterpact circuit breakers can be fed either from the top of the circuit
breaker or from the bottom.
True Two-Step Stored Energy Mechanism: Masterpact circuit breakers are operated via a stored-
energy mechanism which can be manually or motor charged. The closing time is less than five cycles.
Closing and opening operations can be initiated by remote control or by push buttons on the circuit
breaker front cover. An O–C–O cycle is possible without recharging.
Drawout or Fixed Mount, 3-Pole (3P) or 4-Pole (4P) Construction: ANSI Rated, UL Listed and IEC
Rated Masterpact circuit breakers are available in drawout or fixed mounts, with either 3P or 4P
construction.
Field-Installable Trip Units, Sensor Plugs and Accessories: Trip units, sensor plugs and most
accessories are field installable with only the aid of a screwdriver and without adjusting the circuit
breaker. The uniform design of the circuit breaker line allows most accessories to be common for the
whole line.
Reinforced Insulation: Two insulation barriers separate the circuit breaker front from the current path.
Isolation Function by Positive Indication of Contact Status: The mechanical indicator is truly
representative of the status of all the main contacts.
Segregated Compartment: Once the accessory cover has been removed to provide access to the
accessory compartment, the main contacts remain fully isolated. Furthermore, interphase partitioning
allows full insulation between each pole even if the accessory cover has been removed.
Front Connection of Secondary Circuits: All accessory terminals (ring terminals are available as an
option) are located on a connecting block which is accessible from the front in the connected, test and
disconnected positions. This is particularly useful for field inspection and modification.
Anti-Pumping Feature: All Masterpact NT and NW circuit breakers are designed with an anti-pumping
feature that causes an opening order to always takes priority over a closing order. Specifically, if
opening and closing orders occur simultaneously, the charged mechanism discharges without any
movement of the main contacts keeping the circuit breaker in the open (OFF) position.
In the event that opening and closing orders are simultaneously maintained, the standard mechanism
provides an anti-pumping function which continues to keep the main contacts in the open position.
In addition, after fault tripping or opening the circuit breaker intentionally (using the manual or electrical
controls and with the closing coil continuously energized) the circuit breaker cannot be closed until the
power supply to the closing coil is discontinued and then reactivated.
NOTE: When the automatic reset after fault trip (RAR) option is installed, the automatic control system
must take into account the information supplied by the circuit breaker before issuing a new closing
order or before blocking the circuit breaker in the open position. Information on the type of fault, e.g.
overload, short-circuit or ground fault.