Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
25
05/2014
© 2000–2014 Schneider Electric
All Rights Reserved
Micrologic
2.0A, 3.0A, 5.0A, & 6.0A Trip Units with Ammeter
Micrologic A trip units protect power circuits and provide current measurements, overload protection,
and short-circuit protection. In addition, the 6.0A trip units also provide ground-fault protection for
equipment.
Protection Settings
Ammeter Measurements
Micrologic
A trip units measure the true RMS value of currents. They provide continuous current
measurement from 0.2 to 20 x I
n
with an accuracy of 1.5% (including sensors). No auxiliary source is
needed where I > 0.2 x I
n
. The optional external power supply (24 Vdc) makes it possible to display
currents where I < 0.2 x I
n
and to store values of the interrupted current. A digital LCD screen
continuously displays the most heavily loaded phase (Imax) or displays the Ia, Ib, Ic, Ig, and (on 4P circuit
breakers only) In stored current and setting values by successively pressing the navigation button.
Communication Network
Four wire Modbus, RTU, RS485
In conjunction with an optional communication network, the trip unit transmits the following parameters:
Setting values.
All ammeter measurements.
Tripping causes.
NOTE: Current-based protection functions require no auxiliary power source. When an external power
supply is added, the value of the interrupted current is stored by the trip unit. The reset button resets
alarms, and stored interrupted current indications.
1—Test lamp and reset
2—Indication of tripping
cause
3—Digital display
4—Three-phase bar graph
and ammeter
5—Navigation buttons
6—Overload signal (LED)
7—Long-time rating plug
screw
8—Long-time current setting
and tripping delay
9—Short-time pickup and
tripping delay
10—Instantaneous pickup
11—Electronic push-to-trip
12—Ground-fault pickup and
tripping delay
13—Test connector
Protection thresholds and delays are set using the rotary switches. The
selected values are momentarily displayed in amperes and in seconds.
A full-range of long-time settings are available via field-installable rating
plug.
Overload protection (true RMS long-time protection).
Thermal imaging (active thermal imaging before and after tripping).
Short-circuit protection.
Short-time RMS
—I
2
t ON or OFF for short-time delay
Instantaneous protection.
Ground-fault protection for equipment.
Residual ground-fault protection for equipment
Source ground-return ground-fault protection for equipment
Modified differential ground-fault protection (MDGF) for
equipment
Neutral protection on four-pole circuit breakers.
ZSI: Zone-selective interlocking (a ZSI terminal block may be used to
interconnect a number of trip units to provide total discrimination for
short-time and equipment ground-fault protection, without delay for
tripping). Not available for 3.0 A trip unit. Not available for 2.0 A trip
unit if installed as upstream device.
1
3
2
4
5
6
7
8
9
10
11
12
13
Micrologic 6.0A Trip Unit